• Title of article

    A comprehensive design and performance evaluation study of counter flow wet cooling towers

  • Author/Authors

    Khan، نويسنده , , Jameel-Ur-Rehman and Qureshi، نويسنده , , Bilal Ahmed and Zubair، نويسنده , , Syed M.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2004
  • Pages
    10
  • From page
    914
  • To page
    923
  • Abstract
    Fouling of cooling tower fills is one of the most important factors affecting its thermal performance, which reduces cooling tower effectiveness and capability with time. In this paper, the fouling model presented in an earlier paper using the experimental data on fill fouling, is used to investigate the risk based thermal performance of the cooling tower. It is demonstrated that effectiveness of the cooling tower degrades significantly with time indicating that for a low risk level (p=0.01), there is about 6.0% decrease in effectiveness for the given fouling model. The sensitivity analysis of the cooling tower is investigated for both rating and design calculation for different values of mass flow rate ratios. The effect of atmospheric pressure on the thermal performance of the cooling tower is also demonstrated.
  • Keywords
    Tour de refroidissement , Calcul , Performance , Encrassement , Design , Cooling Tower , Performance , FOULING , Conception , CALCULATION
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2004
  • Journal title
    International Journal of Refrigeration
  • Record number