Author/Authors :
Yang، نويسنده , , Liang and Zhang، نويسنده , , Chun-Lu، نويسنده ,
Abstract :
Pronounced hydrodynamic and thermodynamic non-equilibrium exist in the flow of refrigerant through a short tube orifice under typical operating conditions. A non-equilibrium two-fluid model (TFM) for refrigerant two-phase critical flow inside the short tube orifice is developed. Both inter-phase velocity slip and inter-phase temperature difference are taken into account in the model. The mass flow rate, the two-phase velocity and temperature distributions in a short tube orifice are simulated. Comparisons among the experimental data of refrigerants R134a, R12, R22, R410A and R407C flowing through short tubes, the predictions by the TFM and by the homogeneous equilibrium model (HEM) show that the TFM gives acceptable predictions with the deviations of ±20%, while the HEM underestimates the flow rate by 20% or so.
Keywords :
Temperature , R-407C , R-407C , R-134a , R-12 , ةcoulement diphasique , Frigorigène , Two-phase flow , Capillaire , Modelling , Tube , Refrigerant , débit , capillary , Temperature , Distribution , R-410A , Tube , Distribution , Modélisation , R-410A , R-22 , Flow , R-134a , R-12 , R-22