Title of article :
Correction of logarithmic mean temperature difference in a compact brazed plate evaporator assuming heat flux governed flow boiling heat transfer coefficient
Author/Authors :
Claesson، نويسنده , , Joachim، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2005
Pages :
6
From page :
573
To page :
578
Abstract :
The heat transfer in heat exchangers is commonly calculated using the concept of Logarithmic Mean Temperature Difference (LMTD). As is well known this approach is only valid for counter-current and co-current heat exchanger configurations. For other configurations, corrections for the deviation from pure counter-current are introduced. From any standard text book in heat transfer it may be found that the LMTD approach may also be used if condensation and evaporation occurs in the heat exchanger. The purpose of the present paper is to investigate if the LMTD approach can be used in a compact brazed plate evaporator. It will be shown through integration of the governing equations that the LMTD approach indeed may be used for practical cases, even though deviations occur at small logarithmic mean temperature differences. The article presents suggestions on the correction factor (F) needed under some simplified assumptions in a compact brazed plate heat exchanger operating as an evaporator for heat pump and refrigeration applications.
Keywords :
Boiling , ةchangeur à plaque , Coefficient de transfert de chaleur , ةbullition , Plate exchanger , Evaporator , CALCULATION , Temperature difference , Heat transfer coefficient , Calcul , flux thermique , heat flux , ةvaporateur , Différence de température
Journal title :
International Journal of Refrigeration
Serial Year :
2005
Journal title :
International Journal of Refrigeration
Record number :
1339873
Link To Document :
بازگشت