Title of article
Study of a novel silica gel–water adsorption chiller. Part II. Experimental study
Author/Authors
Wang، نويسنده , , D.C. and Wu، نويسنده , , J.Y. and Xia، نويسنده , , Z.Z. and Zhai، نويسنده , , H. and Wang، نويسنده , , R.Z. and Dou، نويسنده , , W.D.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2005
Pages
8
From page
1084
To page
1091
Abstract
The prototype of a novel silica gel–water adsorption chiller is built and its performance is tested in detail. The experimental results show that the refrigerating capacity (RC) and COP of the chiller are 7.15 and 0.38 kW, respectively, when the hot water temperature is 84.8 °C, the cooling water temperature is 30.6 °C, and the chilled water outlet temperature is 11.7 °C. The RC will reach 6 kW under the condition of 65 °C hot water temperature, 30.5 °C cooling water temperature and 17.6 °C chilled water temperature. The results confirm that this kind of adsorption chiller is an effective refrigerating machine though its performance is not as fine as the prediction results. Also it is well effectively driven by a low-grade heat source. Therefore, its applications to the low-grade heat source are much attractive.
Keywords
Experiment , Adsorption system , Silica gel , Performance , Expérimentation , COP , Système à adsorption , water , EAU , Gel de silice , Performance , COP
Journal title
International Journal of Refrigeration
Serial Year
2005
Journal title
International Journal of Refrigeration
Record number
1340093
Link To Document