Title of article
Integration of a three-stage expander into a CO2 refrigeration system
Author/Authors
Nickl، نويسنده , , J. and Will، نويسنده , , G. and Quack، نويسنده , , H. and Kraus، نويسنده , , W.E.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2005
Pages
6
From page
1219
To page
1224
Abstract
The inclusion of an expander with work recovery provides two advantages for transcritical CO2 refrigeration cycles: the COP is improved and the exhaust pressure of the main compressor is lowered. Several designs of expanders have been proposed for this application and some prototypes have been tested already. In our laboratory a three-stage expander has been developed, which replaces the throttle valve of the normal refrigeration cycle and expands into the two-phase region. For optimum integration into the overall system it is proposed to install a vapour-liquid separator between the second and third stage of expansion. The vapour is guided back to the third expander stage whereas the liquid is supplied to the cooling stations via thermostatic or electronic expansion valves.
Keywords
Design , Cycle transcritique , CO2 , Système polyétagé , Transcritical cycle , Expérimentation , CO2 , Multistage system , Refrigerating system , Expander , Turbine à détente , Experiment , Conception , Système frigorifique
Journal title
International Journal of Refrigeration