Title of article :
Condensation heat transfer coefficients of flammable refrigerants
Author/Authors :
Jung، نويسنده , , Dongsoo and Chae، نويسنده , , Soonam and Bae، نويسنده , , Dongsoo and Oho، نويسنده , , Sukjae Jang، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Pages :
4
From page :
314
To page :
317
Abstract :
In this study, external condensation heat transfer coefficients (HTCs) of six flammable refrigerants of propylene (R1270), propane (R290), isobutane (R600a), butane (R600), dimethylether (RE170), and HFC32 were measured at the vapor temperature of 39 °C on a plain tube of 19.0 mm outside diameter with a wall subcooling of 3–8 °C under a heat flux of 7–23 kW m−2. Test results showed a typical trend that external condensation HTCs decrease with the wall subcooling. No unusual behavior or phenomenon was observed for these flammable refrigerants during experiments. HFC32 and DME showed 28–44% higher HTCs than those of HCFC22 due to their excellent thermophysical properties. Propylene and butane showed the similar HTCs as those of HCFC22 while propane and isobutane showed 9% lower HTCs than those of HCFC22. Finally, a general correlation was made by modifying Nusseltʹs equation based upon the measured data of eleven fluids of various vapor pressures including halogenated refrigerants. The general equation showed an excellent agreement with all data exhibiting a deviation of less than 3%.
Journal title :
International Journal of Refrigeration
Serial Year :
2004
Journal title :
International Journal of Refrigeration
Record number :
1341103
Link To Document :
بازگشت