Title of article
Development of an ejector cooling system with thermal pumping effect
Author/Authors
Huang، نويسنده , , B.J. and Hu، نويسنده , , S.S. and Lee، نويسنده , , S.H.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2006
Pages
9
From page
476
To page
484
Abstract
This paper presents a feasibility study of an ejector cooling system (ECS) that utilizes a multi-function generator (MFG) to eliminate the mechanical pump. The MFG serves as both a pump and a vapor generator. The MFG is designed based on the pressure equilibration between high and low pressures through heating and cooling process. In this design, an ECS that contains no moving components and is entirely powered by heat can be practicable. A prototype using refrigerant R141b as working fluid was constructed and tested in the present study. The experimental results showed that the system coefficient of performance (COPo) was 0.218 and the cooling capacity was 0.786 kW at generating temperature (TG) 90 °C, condensing temperature (TC) 32.4 °C and evaporating temperature (TE) 8.2 °C. While taking into account the extra heat needed for the MFG operation, the total coefficient of performance (COPt) is 0.185. It is shown that a continuous operation for the generation of cooling effect in an ECS with MFG can be achieved. This cooling machine can be very reliable since there is no moving part.
Keywords
Générateur , COP , Vapeur , Refrigeration , R-141b , vapour , Froid , R-141b , Ejector system , Generator , système à éjecteur , COP
Journal title
International Journal of Refrigeration
Serial Year
2006
Journal title
International Journal of Refrigeration
Record number
1341160
Link To Document