Title of article :
Dynamic behavior of a direct expansion evaporator under frosting condition. Part I. Distributed model
Author/Authors :
Tso، نويسنده , , C.P. and Cheng، نويسنده , , Y.C. and Lai، نويسنده , , A.C.K.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2006
Pages :
13
From page :
611
To page :
623
Abstract :
A general distributed model with two-phase flow for refrigerant coupled with a frost model is developed for studying the dynamic behavior of an evaporator. The equations are derived in non-steady-state manner for the refrigerant and a quasi-steady state model with permeation for the frost. The complex flow and geometry of the finned tube evaporator lead to uneven wall and air temperature distributions, which in turn affect the rate of frost growth and densification along the coil depth. Results include frost accumulation and its effect on energy transfer, air off-coil temperature, refrigerant liquid dry-out position and propagation of frost formation along the coil.
Keywords :
Two-phase flow , Frost formation , Temperature , heat transfer , Conditionnement dיair , air conditioning , Température , Givrage , ةvaporateur , Evaporator , tube aileté , Refrigeration , Transfert de chaleur , Froid , Modelling , finned tube , Modélisation , ةcoulement diphasique