Title of article :
The effect of stationary and sweeping frequency AC electric fields on frost crystal removal on a cold plate
Author/Authors :
Tudor، نويسنده , , V. and Ohadi، نويسنده , , M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2006
Pages :
9
From page :
669
To page :
677
Abstract :
The effect of stationary and sweeping frequency AC electric fields on frost crystals growth and frost control/removal on a cold plate was studied for the first time in this paper. The main results of this study showed that the presence of AC electric fields can greatly affect both the frost crystals growth pattern and mass accumulation on cold surfaces. The ice surface electrical properties and basic electrostatics were used to explain the main findings in this paper. Up to 46% frost reduction was obtained when the electric field frequency spanned 370 Hz to 7.5 kHz while the applied voltage was 14.5 kV. Two different sets of environmental conditions were tested, which showed that the plate temperature placed an important effect on frost crystals growth under electric fields. An optimum application time of the AC electric fields was found based on least frost mass accumulation on the cold plate.
Keywords :
Plate , Recherche , Electric field , Croissance , Alternating current , Expe´rimentation , De´givrage , givre , Research , Mode´lisation , Experiment , Plaque , Crystal , Courant alternatif , growth , Champ e´lectrique , frost , Defrosting , Modelling , Cristal
Journal title :
International Journal of Refrigeration
Serial Year :
2006
Journal title :
International Journal of Refrigeration
Record number :
1341211
Link To Document :
بازگشت