Title of article :
Frost, defrost, and refrost and its impact on the air-side thermal-hydraulic performance of louvered-fin, flat-tube heat exchangers
Author/Authors :
Xia، نويسنده , , Y. and Zhong، نويسنده , , Y. and Hrnjak، نويسنده , , P.S. and Jacobi، نويسنده , , A.M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2006
Abstract :
The thermal-hydraulic performance under conditions of an initial frost growth on the air-side surface, and for subsequent ‘refrosting’ after a defrost period is experimentally studied for folded-louvered-fin, microchannel heat exchangers. In total, five heat exchangers are considered; the thermal performances during one frost-growth cycle for four different fin geometries are compared in terms of overall heat transfer coefficient, pressure drop, and j and f factors; the defrost and refrost characteristics of two heat exchangers are compared to explore geometry effects. Typically, the performance under refrosting conditions becomes periodic and repeatable after the third or fourth refrosting cycle. The allowable frost growth period (before a defrost is required), the defrost requirement, and the thermal-hydraulic performance depend on heat exchanger geometry for the specimens used in this study.
Keywords :
Air Cooler , Frost formation , finned tube , Defrost , Experiment , heat transfer , ةchangeur de chaleur , refroidisseur dיair , tube aileté , Dégivrage , Expérimentation , Chute de pression , Transfert de chaleur , Givrage , Pressure drop , Heat Exchanger
Journal title :
International Journal of Refrigeration
Journal title :
International Journal of Refrigeration