• Title of article

    Air-side performance of a wavy-finned-tube direct expansion cooling and dehumidifying air coil

  • Author/Authors

    Huzayyin، نويسنده , , A.S. and Nada، نويسنده , , S.A. and Elattar، نويسنده , , H.F.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2007
  • Pages
    15
  • From page
    230
  • To page
    244
  • Abstract
    Airside heat and mass transfer and fluid flow characteristics of a wavy-finned-tube direct expansion air coil under cooling and dehumidifying condition have been experimentally investigated. Experiments were carried out to study the effects of operating conditions such as: air temperature, air relative humidity, air face velocity, and evaporator pressure on the airside performance (cooling capacity, dehumidification capacity, pressure drop, and heat transfer coefficient) of the coil. Charts for coil wet conditions, partially wet or totally wet, were conducted to identify the coil wet conditions in terms of the operating conditions. Two techniques, enthalpy potential method and equivalent dry-bulb temperature method, were used to analyze the data and to deduce correlations for Colburn factors for the different coil wet conditions. Comparison between the correlations predictions of the two techniques was presented.
  • Keywords
    Humid air , heat transfer , Conditionnement dיair , Pressure drop , ةvaporateur , Mass transfer , Expérimentation , tube aileté , Transfert de chaleur , Transfert de masse , air humide , Evaporator , air conditioning , Chute de pression , finned tube , Experiment
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2007
  • Journal title
    International Journal of Refrigeration
  • Record number