• Title of article

    Development of type 2 solution transportation absorption system for utilizing LNG cold energy

  • Author/Authors

    Jo، نويسنده , , Young Kyong and Kim، نويسنده , , Jin-Kyeong and Lee، نويسنده , , Soon Geul and Kang، نويسنده , , Yong Tae، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2007
  • Pages
    8
  • From page
    978
  • To page
    985
  • Abstract
    The objective of this paper is to develop a new energy transport system for district cooling application by using type 2 absorption cycle. Cold energy from the LNG storage system is utilized as the cooling source of the condenser and the rectifier. The pressures of the system, UAs of the evaporator and the desorber, the inlet temperatures of the refrigerant for each component, transportation distance and the pumping power per unit length are considered as the key parameters. The results show that UA of the evaporator has more dominant effect on COP than that of the desorber. The optimum system pressure for the demand side is also determined. For the present system, it is recommended that the refrigerant inlet temperature of the evaporator be lower than 4.3 °C for long distance transportation. It is concluded that the cold energy from the LNG storage system can be effectively applied to the long distance transportation system for district cooling application with the type 2 absorption cycle. The maximum transportation distance and the pumping power per unit length are calculated. The optimum operation conditions are also predicted from the parametric analysis.
  • Keywords
    District cooling , Design , Absorption System , Ammonia–water , Heat source , Condenser , Froid urbain , Conception , Système à absorption , LNG , Ammoniac–eau , GNL , Source de chaleur , Condenseur
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2007
  • Journal title
    International Journal of Refrigeration
  • Record number