Title of article
Thermodynamic analysis of an R744–R717 cascade refrigeration system
Author/Authors
Getu، نويسنده , , H.M. and Bansal، نويسنده , , P.K.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2008
Pages
10
From page
45
To page
54
Abstract
A thermodynamic analysis of carbon dioxide–ammonia (R744–R717) cascade refrigeration system is presented in this paper to optimize the design and operating parameters of the system. The design and operating parameters considered in this study include (1) condensing, subcooling, evaporating and superheating temperatures in the ammonia (R717) high-temperature circuit, (2) temperature difference in the cascade heat exchanger, and (3) evaporating, superheating, condensing and subcooling in the carbon dioxide (R744) low-temperature circuit. A multilinear regression analysis was employed in terms of subcooling, superheating, evaporating, condensing, and cascade heat exchanger temperature difference in order to develop mathematical expressions for maximum COP, an optimum evaporating temperature of R717 and an optimum mass flow ratio of R717 to that of R744 in the cascade system.
Keywords
CALCULATION , optimization , Performance , Système frigorifique , Système à compression , Ammoniac , Dioxyde de carbone , R744 , Calcul , Refrigeration system , Performance , Compression system , Optimisation , Ammonia , Carbon dioxide , R744 , Cascade system , Système en cascade
Journal title
International Journal of Refrigeration
Serial Year
2008
Journal title
International Journal of Refrigeration
Record number
1341696