Title of article
Performance optimization of a hybrid cooler combining vapor compression and natural circulation cycles
Author/Authors
Lee، نويسنده , , Sunil and Kang، نويسنده , , Hoon Sik Kim، نويسنده , , Yongchan، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2009
Pages
9
From page
800
To page
808
Abstract
A hybrid cooler combining vapor compression and natural circulation cycles was developed for the cooling of telecommunication equipment in the cabinet-type base station of mobile communication. This hybrid cooler normally operates in the vapor compression mode at high ambient temperatures, but works in the natural circulation mode at low ambient temperatures by the thermosiphon principle. The performance of the hybrid cooler was measured according to the refrigerant charge, outdoor temperature, heat exchanger geometry, and the vertical distance between the condenser and the evaporator. The optimum design conditions for these variables are discussed with respect to the performance of the hybrid cooler in both operating modes. The difference in the optimum refrigerant charge between the two operating modes was solved by installing a liquid receiver. The temperature difference between the indoor and ambient air was introduced as a control parameter for use when changing the operating mode.
Keywords
COMPONENT , electronic , Telecommunications , Compression system , Thermosiphon , Experiment , Composant , ةlectronique , Système frigorifique , Télécommunication , Système à compression , Thermosiphon , COOLING , Refroidissement , Cooling System , Expérimentation
Journal title
International Journal of Refrigeration
Serial Year
2009
Journal title
International Journal of Refrigeration
Record number
1342271
Link To Document