Title of article :
An experimental study of the enhanced heating capacity of an electric heat pump (EHP) using the heat recovered from a gas engine generator
Author/Authors :
Kim، نويسنده , , Cheol Min and Lee، نويسنده , , Jaekeun and Chang، نويسنده , , Se Dong and Hwang، نويسنده , , Yujin، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2009
Pages :
9
From page :
1702
To page :
1710
Abstract :
This paper is concerned with the effect of recovered heat on the heating capacity of an Electric Heat Pump (EHP), which is supplied with electric power and recovered heat from a gas engine generator system. Two methods of supplying recovery heat are examined: (i) to the refrigerant with the discharge line heat exchanger (HEX), and (ii) to the refrigerant of the evaporator with the sub-evaporator. Heating capacity, input power and coefficient of performance (COP) were investigated and compared for each heat recovery method. Conclusively, we found that the second method was most reasonable to recover wasted heat and increased system COP by 215%.
Keywords :
Pompe à chaleur , Gas engine , Expérimentation , Moteur à gaz , Cogénération , Récupération de chaleur , Air–air , Heat pump , Air–air , Experiment , Cogeneration , Heat recovery
Journal title :
International Journal of Refrigeration
Serial Year :
2009
Journal title :
International Journal of Refrigeration
Record number :
1342394
Link To Document :
بازگشت