• Title of article

    Improved methodologies for simulating unitary air conditioners at off-design conditions

  • Author/Authors

    Shen، نويسنده , , Bo and Braun، نويسنده , , James E. and Groll، نويسنده , , Eckhard A.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2009
  • Pages
    13
  • From page
    1837
  • To page
    1849
  • Abstract
    Models for unitary air conditioners and heat pumps typically have difficulties in providing accurate predictions for the following situations: 1) charge modeling over a large range of charge levels, 2) two-phase refrigerant entering fixed-orifice expansion devices, 3) two-phase refrigerant entering compressors, and 4) non-uniform refrigerant mass flow allocation among evaporator circuits at low indoor air flow rates. This paper gives descriptions and assessments of improved modeling methodologies for all four issues. The study utilizes data obtained from extensive testing at a wide range of operating conditions for two R-410A units and one R-407C unit.
  • Keywords
    Simulation , Operation , Variation , Refrigerant charge , flow rate , Conditionnement dיair , Conditionneur dיair , Modélisation , Fonctionnement , Charge en frigorigène , Variation , débit , air conditioning , Modelling , Simulation , Air conditioner
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2009
  • Journal title
    International Journal of Refrigeration
  • Record number