Title of article
Improved methodologies for simulating unitary air conditioners at off-design conditions
Author/Authors
Shen، نويسنده , , Bo and Braun، نويسنده , , James E. and Groll، نويسنده , , Eckhard A.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2009
Pages
13
From page
1837
To page
1849
Abstract
Models for unitary air conditioners and heat pumps typically have difficulties in providing accurate predictions for the following situations: 1) charge modeling over a large range of charge levels, 2) two-phase refrigerant entering fixed-orifice expansion devices, 3) two-phase refrigerant entering compressors, and 4) non-uniform refrigerant mass flow allocation among evaporator circuits at low indoor air flow rates. This paper gives descriptions and assessments of improved modeling methodologies for all four issues. The study utilizes data obtained from extensive testing at a wide range of operating conditions for two R-410A units and one R-407C unit.
Keywords
Simulation , Operation , Variation , Refrigerant charge , flow rate , Conditionnement dיair , Conditionneur dיair , Modélisation , Fonctionnement , Charge en frigorigène , Variation , débit , air conditioning , Modelling , Simulation , Air conditioner
Journal title
International Journal of Refrigeration
Serial Year
2009
Journal title
International Journal of Refrigeration
Record number
1342407
Link To Document