Title of article :
Thermodynamic studies on NH3–H2O absorption cooling system using pinch point approach
Author/Authors :
Jawahar، نويسنده , , C.P. and Raja، نويسنده , , B. and Saravanan، نويسنده , , R.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2010
Pages :
9
From page :
1377
To page :
1385
Abstract :
An ammonia–water (NH3–H2O) absorption cooling system is analyzed using the pinch point analysis, to recover maximum internal heat from the streams, thereby increasing the system performance. The system is simulated for generator temperatures between 120 °C and 150 °C, sink temperatures between 25 °C and 45 °C and evaporator temperatures between −10 °C and 10 °C. Based on the maximum internal heat that could be obtained using this approach the conventional cycle is modified without the need for rectification and its performance is compared. The coefficient of performance (COP) of the proposed cycle is found to be 17 to 56% higher than that of a conventional cycle with respect to the operating conditions analyzed.
Keywords :
Simulation-performance , COP , Récupération de chaleur , Absorption System , Simulation-performance , Ammonia–water-modelling , Heat recovery , Ammoniac–eau-modélisation , Système à absorption , COP