Performance of residential air-conditioning systems with flow maldistribution in fin-and-tube evaporators
Author/Authors :
Wiebke and Kوrn، نويسنده , , Martin Ryhl and Brix، نويسنده , , Wiebke and Elmegaard، نويسنده , , Brian T. Larsen، نويسنده , , Lars Finn Sloth، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2011
Pages :
11
From page :
696
To page :
706
Abstract :
Refrigerant and airflow maldistribution in fin-and-tube evaporators for residential air-conditioning was investigated with numerical modeling. Fin-and-tube heat exchangers usually have a pre-defined circuitry. However, the objective in this study was to perform a generic investigation of each individual maldistribution source in an independent manner. Therefore, the evaporator and the condenser were simplified to be straight tubes for the purposes of this study. The numerical model of the R410A system, its verification and an investigation of individual maldistribution sources are presented in this paper. The maldistribution sources of interest were: inlet liquid/vapor phase distribution, feeder tube bending and airflow distribution. The results show that maldistribution reduced the cooling capacity and the coefficient of performance of the system. In particular, different phase distribution and non-uniform airflow distribution reduced the performance significantly. Different feeder tube bendings only caused a minor decrease in performance.
Keywords :
Modélisation , SIMULATION , COOLING , finned tube , SIMULATION , Conditionnement dיair , Distribution , air conditioning , tube aileté , MODELING
Journal title :
International Journal of Refrigeration
Serial Year :
2011
Journal title :
International Journal of Refrigeration
Record number :
1342910
Link To Document :
بازگشت