• Title of article

    A study of transcritical carbon dioxide flow through diabatic capillary tubes

  • Author/Authors

    da Silva، نويسنده , , Diogo L. and Ronzoni، نويسنده , , Adriano F. and Melo، نويسنده , , Clلudio and Hermes، نويسنده , , Christian J.L.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2011
  • Pages
    10
  • From page
    834
  • To page
    843
  • Abstract
    An experimental and theoretical study of the diabatic flow of carbon dioxide through lateral capillary tube suction line heat exchangers is outlined. The influence of both operating conditions (capillary tube inlet and outlet pressures, capillary tube inlet temperature and suction line inlet temperature) and tube geometry (heat exchanger length and position, suction line diameter and capillary tube length) on the heat and mass flow rates was experimentally evaluated using a purpose-built testing facility. In total, 75 tests were carried out with heat fluxes spanning from 1 to 11 kW m−2 and refrigerant mass flow rates ranging from 12 to 26 kg h−1. In addition, the mathematical model of Hermes et al. (2008) was adapted to run with carbon dioxide as working fluid. The model was validated against experimental data, and a good agreement between the experimental and calculated mass flow rates was achieved with 85% and 98% of the data points being within ±5% and ±10% error bounds, respectively.
  • Keywords
    Carbon dioxide , EXPANSION , Heat Exchanger , Dioxyde de carbone , Détente , Tube capillaire , échangeur de chaleur , Capillary tube
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2011
  • Journal title
    International Journal of Refrigeration
  • Record number