Title of article
A new method for preventing air-source heat pump water heaters from frosting
Author/Authors
Zhang، نويسنده , , Li and Fujinawa، نويسنده , , Takeshi and Saikawa، نويسنده , , Michiyuki، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2012
Pages
8
From page
1327
To page
1334
Abstract
This paper proposes a frost-free air-source heat pump water heater (ASHPWH) system with integrated solid desiccant, in which frosting can be retarded by dehumidifying air before it enters the ASHPWH evaporator. The system consists of a conventional heat pump water heater and an extra heat exchanger coated by a solid desiccant. During the desorption process of the desiccant, regeneration air is cycled between the desiccant-coated heat exchanger and the evaporator to recover the sensible heat and latent heat of the regeneration air. A numerical simulation is carried out at a dry-bulb temperature of −7 °C–5.5 °C and a relative humidity of 60%–80% depending on the frosting conditions. The results show that the coefficient of performance (COP) is within the range 3.3–3.8, which is 5–30% higher than that of the ASHPWH system using the hot-gas defrosting method.
Keywords
desiccant , frost , SIMULATION , Déshydratant , givre , Pompe à chaleur , Eau chaude , Heat pump , SIMULATION , Hot water
Journal title
International Journal of Refrigeration
Serial Year
2012
Journal title
International Journal of Refrigeration
Record number
1344591