• Title of article

    A new method for preventing air-source heat pump water heaters from frosting

  • Author/Authors

    Zhang، نويسنده , , Li and Fujinawa، نويسنده , , Takeshi and Saikawa، نويسنده , , Michiyuki، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2012
  • Pages
    8
  • From page
    1327
  • To page
    1334
  • Abstract
    This paper proposes a frost-free air-source heat pump water heater (ASHPWH) system with integrated solid desiccant, in which frosting can be retarded by dehumidifying air before it enters the ASHPWH evaporator. The system consists of a conventional heat pump water heater and an extra heat exchanger coated by a solid desiccant. During the desorption process of the desiccant, regeneration air is cycled between the desiccant-coated heat exchanger and the evaporator to recover the sensible heat and latent heat of the regeneration air. A numerical simulation is carried out at a dry-bulb temperature of −7 °C–5.5 °C and a relative humidity of 60%–80% depending on the frosting conditions. The results show that the coefficient of performance (COP) is within the range 3.3–3.8, which is 5–30% higher than that of the ASHPWH system using the hot-gas defrosting method.
  • Keywords
    desiccant , frost , SIMULATION , Déshydratant , givre , Pompe à chaleur , Eau chaude , Heat pump , SIMULATION , Hot water
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2012
  • Journal title
    International Journal of Refrigeration
  • Record number

    1344591