• Title of article

    Improved energy performance of air-cooled water chillers with innovative condenser coil configurations – Part ΙΙ: Experimental validation

  • Author/Authors

    Lee، نويسنده , , Tzong-Shing and Wu، نويسنده , , Wu-Chieh and Jiang، نويسنده , , Jin-Cheng، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2012
  • Pages
    11
  • From page
    2212
  • To page
    2222
  • Abstract
    The second part of this study (Part II) used full-scale experimentation to investigate the manner in which how two condenser coil configurations (VRC and CRC) influence the performance (energy efficiency) of the system and individual components of air-cooled chillers. The results showed that, for both DX and FL evaporator configurations, the chillers with VRC condensers had a greater cooling capacity (an increase of 4.5% and 4.0%, respectively), refrigeration capacity (an increase of 6.5% and 5.6%, respectively), and COP (an increase of 7.3% and 6.7%, respectively), compared to chillers using CRC condensers. This demonstrates that VRC-designed condensers can effectively improve heat transfer performance and enhance the energy efficiency of refrigeration systems without increasing material costs or the number of tubes and fans. The results of this study can be used as reference data for future research on improving the system performance of air-cooled water chillers.
  • Keywords
    configuration , Analyse de lיexergie , Coefficient de performance , Irréversibilité , Chiller , Air-cooled , configuration , Variant rows , Irreversibility , Exergy analysis , Coefficient of Performance , Refroidisseur , Refroidi à lיair , Rangées
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2012
  • Journal title
    International Journal of Refrigeration
  • Record number