Title of article :
Experimental investigation of the temperatures and performance of a commercial ice-storage tank
Author/Authors :
Lَpez-Navarro، نويسنده , , A. and Biosca-Taronger، نويسنده , , J. and Torregrosa-Jaime، نويسنده , , B. and Martيnez-Galvلn، نويسنده , , I. and Corberلn، نويسنده , , J.M. and Esteban-Matيas، نويسنده , , J.C. and Payل، نويسنده , , J.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2013
Pages :
9
From page :
1310
To page :
1318
Abstract :
This paper presents the results of an experimental installation with an internal melt-ice-on-coil tank which has a total capacity of 172 kWh. The aim of this work is to analyse the freezing process in a tank with counter-current spiral-shaped coils immersed in around 1855l water. An experimental campaign has been performed with different inlet temperatures and mass flow rates of the heat transfer fluid. This study analyses (i) the chiller performance, (ii) the ice-formation process and (iii) the energy consumption of the installation. Supply temperatures between −2.5 °C and −5.2 °C have been sufficient to charge the tank without using any nucleating agents. The lowest energy consumption has been achieved for the fastest charging tests.
Keywords :
Thermal storage , Ice formation , Energy consumption , Accumulation thermique , formation de glace , consommation dיénergie , installation expérimentale , Experimental installation
Journal title :
International Journal of Refrigeration
Serial Year :
2013
Journal title :
International Journal of Refrigeration
Record number :
1345261
Link To Document :
بازگشت