• Title of article

    In situ measurement methods of air to air heat pump performance

  • Author/Authors

    Tran، نويسنده , , C.T. and Rivière، نويسنده , , P. and Marchio، نويسنده , , D. and Arzano-Daurelle، نويسنده , , C.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2013
  • Pages
    14
  • From page
    1442
  • To page
    1455
  • Abstract
    There is no in situ reliable measurement method of air-to-air heat pump heating performances. This paper tests and validates two methods in laboratory and in steady-state conditions. The first method based on refrigerant fluid measurements determines the refrigerant flow rate by using the compressor thermal balance. In particular, the evaporation pressure is measured by a saturation temperature measurement and the compressor ambient heat losses are evaluated from the heat exchanges. The method uses only non-intrusive sensors, except for the condensation pressure sensor installed at the refrigerant charging plug. The second method based on air measurements determines the air flow rate via a multi-point velocity measurement. According to the experimental results, these methods are fully applicable on field with deviations of 4% and 10%, for the refrigerant method and the air method respectively, when compared to the “etalon” measurement.
  • Keywords
    Experimentation , Refrigerant , mesures in situ , Moist air , Performance , Frigorigène , air humide , Expérience , Heat pump , Performance , In situ measurement , Pompe à chaleur
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2013
  • Journal title
    International Journal of Refrigeration
  • Record number