Title of article :
Proposal of an eco-friendly high-performance air-conditioning system. Part 1. Possibility of improving existing air-conditioning system by an evapo-transpiration condenser
Author/Authors :
Minh Thu، نويسنده , , Huynh Thi and Sato، نويسنده , , Haruki، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2013
Pages :
7
From page :
1589
To page :
1595
Abstract :
Air-conditioning (AC) system consumes high energy and releases waste-heat. In the present study, we propose a method to improve its performance and minimize waste-heat by replacing existing air-cooled condenser by an evaporation and transpiration, evapo-transpiration, condenser. The improvement is confirmed by performing experiment for a conventional air-cooled AC system and a water-cooled AC system. Condenser temperature in the air-cooled system is higher than outdoor-temperature by 5–10 °C, while it is −5 to 5 °C in case of the testing system. From simulation results, saving energy consumption is expected to reach up to 30% in summer with the testing system. Based on these results, an evapo-transpiration heat-exchanger was developed as a new condenser. Heat-transfer coefficient of the testing heat-exchanger is at least 4 times higher than that of air-cooled condenser. Even hot fluid is used inside copper-tubing, its outlet-air temperature is as nearly as outdoor temperature.
Keywords :
exergie , Condenseur , ENERGY SAVING , Air-conditioning , Condenser , Heat island , evapo-transpiration , Exergy , Conditionnement d’air , îlot de chaleur , économies d’énergie , évapotranspiration
Journal title :
International Journal of Refrigeration
Serial Year :
2013
Journal title :
International Journal of Refrigeration
Record number :
1345367
Link To Document :
بازگشت