• Title of article

    Improved energy performance of a refrigerating machine using water spray upstream of the condenser

  • Author/Authors

    Tissot، نويسنده , , J. and Boulet، نويسنده , , P. and Trinquet، نويسنده , , F. and Fournaison، نويسنده , , L. and Lejeune، نويسنده , , M. and Liaudet، نويسنده , , F.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2014
  • Pages
    13
  • From page
    93
  • To page
    105
  • Abstract
    An experimental and numerical study has been carried out on the improvement of the energy performance of a refrigerating machine using a water spray upstream of the condenser. The experimental setup is based on a reversible heat pump used in cooling mode. The spray has been simply added upstream from the heat pump in order to investigate the possible performance improvements on a real machine, leaving its own control system free to adapt itself. Condensation temperature and pressure data have been measured on the refrigerating fluid side, while temperature and humidity have been measured on the air upstream and downstream the condenser. A complete model has been developed, combining a thermodynamic model for the system and heat transfer models on the air and refrigerating fluid sides. Comparisons have been carried out. Results show that water spraying upstream of the condenser may increase the global COP of the system (refrigerating machine plus spraying system) up to 28.9% for relatively hot and dry air conditions (relative humidity 19,7% and temperature 308 K).
  • Keywords
    Energy , Pompe à chaleur , Condenseur , Aspersion , Energie , Evaporation , Heat pump , Spray , Condenser , Evaporation
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2014
  • Journal title
    International Journal of Refrigeration
  • Record number

    1345818