Title of article
New absorption chiller and control strategy for the solar assisted cooling system at the German federal environment agency
Author/Authors
Albers، نويسنده , , Jan، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2014
Pages
9
From page
48
To page
56
Abstract
Typically the cooling capacity of absorption chillers is controlled by adjusting the driving hot water temperature according to the load. Meanwhile the cooling water temperature is controlled to a constant set value. In order to increase the solar cooling fraction and/or to decrease the operating costs of solar assisted cooling systems (SAC-systems) a new control strategy has been developed which controls hot and cooling water temperature simultaneously. Hereby the specific cost of cold – generated from solar or conventional heat – can be reduced. The basic concept of the strategy is explained and results are shown for the SAC-system at the Federal Environment Agency in Dessau, Germany. Here a recently developed absorption chiller is now used instead of a former adsorption chiller. With the new absorption chiller and the control strategy the seasonal energy efficiency ratio SEER is above 0.75, electric efficiency is 35% higher and water consumption is reduced by 70%.
Keywords
Surveillance , absorption chiller , Adsorption chiller , Monitoring , control strategy , Cold price , Refroidisseur à absorption , Refroidisseur à adsorption , Prix du froid , Stratégie de régulation
Journal title
International Journal of Refrigeration
Serial Year
2014
Journal title
International Journal of Refrigeration
Record number
1345898
Link To Document