• Title of article

    New absorption chiller and control strategy for the solar assisted cooling system at the German federal environment agency

  • Author/Authors

    Albers، نويسنده , , Jan، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2014
  • Pages
    9
  • From page
    48
  • To page
    56
  • Abstract
    Typically the cooling capacity of absorption chillers is controlled by adjusting the driving hot water temperature according to the load. Meanwhile the cooling water temperature is controlled to a constant set value. In order to increase the solar cooling fraction and/or to decrease the operating costs of solar assisted cooling systems (SAC-systems) a new control strategy has been developed which controls hot and cooling water temperature simultaneously. Hereby the specific cost of cold – generated from solar or conventional heat – can be reduced. The basic concept of the strategy is explained and results are shown for the SAC-system at the Federal Environment Agency in Dessau, Germany. Here a recently developed absorption chiller is now used instead of a former adsorption chiller. With the new absorption chiller and the control strategy the seasonal energy efficiency ratio SEER is above 0.75, electric efficiency is 35% higher and water consumption is reduced by 70%.
  • Keywords
    Surveillance , absorption chiller , Adsorption chiller , Monitoring , control strategy , Cold price , Refroidisseur à absorption , Refroidisseur à adsorption , Prix du froid , Stratégie de régulation
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2014
  • Journal title
    International Journal of Refrigeration
  • Record number

    1345898