Title of article :
Energy consumption model of integrated air conditioner with thermosyphon in mobile phone base station
Author/Authors :
Han، نويسنده , , Linjun and Shi، نويسنده , , Wenxing and Wang، نويسنده , , Baolong and Zhang، نويسنده , , Penglei and Li، نويسنده , , Xianting، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2014
Abstract :
Data centers and mobile phone base stations (MBS) are consuming more and more energy due to the development of the information communication technology (ICT) industry. The integrated air conditioner with thermosyphon (IACT) was proposed as an efficient cooling device for these spaces, combining vapor compression (VC) refrigeration with a thermosyphon (TS). In this paper, a model to simulate the annual energy consumption of IACT is built and compared with the traditional air conditioner (TAC) in four standard MBSs located in the typical climate zones of China. The results show that the IACT saves 19.1%–28.2% more energy than the TAC, and in hotter regions has a larger energy saving amount but a smaller energy saving rate (ESR). The TS mode works effectively when the mean monthly temperature is 5.4 °C–24.5 °C. The monthly ESR of IACT in the MBSs of Beijing and Guangzhou is 12.2%–48.6% and 12.1%–45.2% respectively.
Keywords :
Integrated air conditioner , Energy consumption , Simulation , Thermosiphon , consommation dיénergie , Simulation , Conditionneur dיair intégré , thermosyphon
Journal title :
International Journal of Refrigeration
Journal title :
International Journal of Refrigeration