Title of article
Indoor unit fault detector for a multi-split VRF system in heating mode
Author/Authors
Shin، نويسنده , , Younggy and Karng، نويسنده , , Sarng Woo and Kim، نويسنده , , Seo Young، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2014
Pages
9
From page
152
To page
160
Abstract
A multi-split VRF system operates unsteadily most of time due to the constantly varying refrigerant flow rates of associated indoor units. VRF systems require a different approach from conventional techniques to detect faults, which have developed based on steady-state operations. In this paper, two fault detection techniques are proposed. Their advantage is that they do not require the test data to be preprocessed to obtain steady-state data. The first technique is applied to detect heat exchanger fouling by a state observer, and the other technique is used to detect valve sticking by temperature variance. These techniques were not chosen haphazardly but were derived from physical reasoning. Their validity was confirmed by test data. The methodology developed in this study can be applied similarly to other HVAC equipment that operates mostly in transient states.
Keywords
Détection de défaut et diagnostic , Encrassage des échangeurs de chaleur , Observateur dיétat , débit variable de frigorigène , Pompe à chaleur , FDD (fault detection and diagnosis) , Heat exchanger fouling , State observer , Multi-split , Heat pump , VRF (variable refrigerant flow) , Multi-split
Journal title
International Journal of Refrigeration
Serial Year
2014
Journal title
International Journal of Refrigeration
Record number
1345973