• Title of article

    Numerical and experimental investigation on nozzle parameters for R410A ejector air conditioning system

  • Author/Authors

    Hu، نويسنده , , Jichao and Shi، نويسنده , , Junye and Liang، نويسنده , , Yuanyuan and Yang، نويسنده , , Zijiang and Chen، نويسنده , , Jiangping، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2014
  • Pages
    9
  • From page
    338
  • To page
    346
  • Abstract
    The experimental and numerical study on R410A air conditioning system with two-phase ejector were presented in this paper. An adjustable liquid–gas ejector based on a two-phase flow simulation model was designed and manufactured for experiment in the R410A air conditioning system. Both throat diameter (Dnt) and position (Dnm) of nozzle were studied under the given conditions. The experimental results showed that Dnt of 1 mm and Dnm of 4 mm yielded the best ejector efficiency and system EER. Nozzles with different Dnt and the adjustable ejector were also studied under different conditions. The experimental results showed that the ejector with adjustable nozzle can meet the requirements of different operation conditions. It was very useful for the future application of ejector in the air conditioning system.
  • Keywords
    Ejecteur diphasique , Entrainment ratio , Adjustable ejector , Ejecteurs ajustables , Ratio dיentraînement , Paramètres des tuyères , Two-phase ejector , Nozzle parameters , R410A , R410A
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2014
  • Journal title
    International Journal of Refrigeration
  • Record number

    1346035