Title of article :
Mode localization of a component cooling water heat exchanger
Author/Authors :
Huang، نويسنده , , Bo-Wun and Kung، نويسنده , , Huang-Kuang Kung، نويسنده ,
Issue Information :
ماهنامه با شماره پیاپی سال 2005
Pages :
17
From page :
170
To page :
186
Abstract :
In a nuclear power plant, the tubes of a component cooling water heat exchanger are frequently affected by cold and hot fluid shock waves. Thus, tubes are often found to be worn out. This wear may alter the dynamics of the tubes and introduce mode localization in the heat exchanger. This paper examines mode localization in a component cooling water heat exchanger. A heat exchanger, consisting of periodic cooling tubes is used to simulate as a coupled periodic structure system. Each tube is coupled to the adjacent one through the water, and so the system is weakly coupled. The Galerkin method is employed herein to derive the mode localization equations off the mistuned system, with reference to the fluid effect. Numerical results reveal that the wear may introduce mode localization into a mistuned heat exchanger with fluid.
Keywords :
Modal localization , Heat Exchanger , disorder
Journal title :
International Journal of Mechanical Sciences
Serial Year :
2005
Journal title :
International Journal of Mechanical Sciences
Record number :
1416415
Link To Document :
بازگشت