Title of article :
Mercury emissions from a 100-MW wall-fired boiler as measured by semicontinuous mercury monitor and Ontario Hydro Method
Author/Authors :
Kellie، نويسنده , , Shawn and Duan، نويسنده , , Yufeng and Cao، نويسنده , , Yan and Chu، نويسنده , , Paul and Mehta، نويسنده , , Arun and Carty، نويسنده , , Ron and Liu، نويسنده , , Kunlei and Pan، نويسنده , , Wei-Ping and Riley، نويسنده , , John T.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Pages :
13
From page :
487
To page :
499
Abstract :
Western Kentucky University (WKU) recently established a mobile laboratory for monitoring mercury emissions (MMEML). The lab contains facilities to perform both continuous emissions monitoring and the Ontario Hydro Method for mercury analysis. Among the instruments available in the lab are a semicontinuous mercury emissions monitor (SCEM), pretreatment and speciation unit for the SCEM, and an atomic absorption spectrometer with automated sampler. The MMEML was recently utilized at a power plant site that had a 100-MW, wall-fired combustor with low-NOx burners. At this site, a comparison between OHM and SCEM data was possible for testing locations before and after the ESP. OHM and SCEM produced analogous results for the measurement of total mercury, but differ in their measurement of mercury speciation. Testing by OHM also showed that vapor-phase mercury decreases as temperature decreases and as fly ash is removed. Our results suggest that the removal of vapor-phase mercury by fly ash is mostly the removal of oxidized mercury.
Keywords :
MMEML , Ontario Hydro Method , SCEM
Journal title :
Fuel Processing Technology
Serial Year :
2004
Journal title :
Fuel Processing Technology
Record number :
1506404
Link To Document :
بازگشت