Title of article
High energy pipe break analysis for a Main Steam Line of a WWER NPP
Author/Authors
Zaccari، نويسنده , , N. and Caria، نويسنده , , S. and Rubeo، نويسنده , , G.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2014
Pages
12
From page
100
To page
111
Abstract
The aim of this study is to show the application of the High Energy Pipe Break (HEPB) methodology to a level 3 analysis, applied to the study of the Main Steam Line (MSL) of a Mochovce (MO) NPP. The analysis highlighted the significant advantage, as compared to a standard level 1 analysis, in the minimization of extra supports and restraints. In the first part of the paper an introduction on the NUREG Standard Review Plan (STRP) and on the ANSI/ANS 58.2 used as a reference in this kind of analysis is provided. In the second part a description of the analyses (coupled mechanical and fluido-dynamic) used to analyze the HEPB is described. Finally an original approach developed at ENEL is presented for an improved evaluation of the leakage cracking by following a non standard procedure related to the LBB approach, coupled with the above-mentioned HEPB.
Journal title
Nuclear Engineering and Design Eslah
Serial Year
2014
Journal title
Nuclear Engineering and Design Eslah
Record number
1593937
Link To Document