Title of article
Heat transfer studies on a GAXAC (generator-absorber-exchange absorption compression) cooler
Author/Authors
Rameshkumar، نويسنده , , A. and Udayakumar، نويسنده , , M. and Saravanan، نويسنده , , R.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2009
Pages
9
From page
2056
To page
2064
Abstract
A detailed heat transfer model of GAXAC (generator-absorber-exchange absorption compression) cycle using ammonia–water as working fluid is reported. The effect of UA (heat transfer conductance, kW/K) of each component on COP and cycle capacity is investigated. The results show that UA of the absorber and high temperature generator (HTG) have significant impact on COP and cycle capacity. For a capacity of 11.56 kW, the maximized COP with minimum UA value for all heat exchanging components is found to be 1.185. Further the effect of mass flow rate and inlet temperatures of hot fluid, chilled water and cooling water are also investigated.
Keywords
Ammonia–water , GAX , UA , Absorption–compression , Heat transfer model