Title of article :
Performance of heat pumps charged with R170/R290 mixture
Author/Authors :
Park، نويسنده , , Ki-Jung and Jung، نويسنده , , Dongsoo، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2009
Abstract :
In this study, thermodynamic performance of R170/R290 mixture is measured on a heat pump bench tester in an attempt to substitute R22. The bench tester is equipped with a commercial hermetic rotary compressor providing a nominal capacity of 3.5 kW. All tests are conducted under the summer cooling and winter heating conditions of 7/45 °C and −7/41 °C in the evaporator and condenser, respectively. During the tests, the composition in R170/R290 mixture is varied from 0% to 10% with an interval of 2%. Test results show that the coefficient of performance (COP) and capacity of R290 are up to 15.4% higher and 7.5% lower, respectively than those of R22 for two conditions. For R170/R290 mixture, the COP decreases and the capacity increases with an increase in the composition of R170. The mixture of R170/R290 mixture at 4%/96% composition shows the similar capacity and COP as those of R22. For the mixture, the compressor discharge temperature is 17–28 °C lower than that of R22. For R170/R290 mixture, there is no problem with mineral oil since the mixture is composed of hydrocarbons. The amount of charge is reduced up to 58% as compared to R22. Overall, R170/R290 mixture is a good long term ‘drop-in’ candidate from the view point of energy efficiency and greenhouse warming to replace R22 in residential air-conditioners and heat pumps.
Keywords :
alternative refrigerant , COP , Capacity , R170 (ethane) , Refrigerant mixture , R290 (propane) , Heat pump
Journal title :
Applied Energy
Journal title :
Applied Energy