Title of article :
The effects of operation parameter on the performance of a solar-powered adsorption chiller
Author/Authors :
Luo، نويسنده , , Huilong and Wang، نويسنده , , Ruzhu and Dai، نويسنده , , Yanjun، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2010
Pages :
5
From page :
3018
To page :
3022
Abstract :
A solar-powered adsorption chiller with heat and mass recovery cycle was designed and constructed. It consists of a solar water heating unit, a silica gel-water adsorption chiller, a cooling tower and a fan coil unit. The adsorption chiller includes two identical adsorption units and a second stage evaporator with methanol working fluid. The effects of operation parameter on system performance were tested successfully. Test results indicated that the COP (coefficient of performance) and cooling power of the solar-powered adsorption chiller could be improved greatly by optimizing the key operation parameters, such as solar hot water temperature, heating/cooling time, mass recovery time, and chilled water temperature. Under the climatic conditions of daily solar radiation being about 16–21 MJ/m2, this solar-powered adsorption chiller can produce a cooling capacity about 66–90 W per m2 collector area, its daily solar cooling COP is about 0.1–0.13.
Keywords :
Solar cooling , Operation parameter , Coefficient of Performance , Mass recovery , Heat recovery , Silica gel
Journal title :
Applied Energy
Serial Year :
2010
Journal title :
Applied Energy
Record number :
1604358
Link To Document :
بازگشت