Title of article :
The cooling seasonal performance factor of a hybrid ground-source heat pump with parallel and serial configurations
Author/Authors :
Park، نويسنده , , Honghee and Lee، نويسنده , , Joo Seoung and Kim، نويسنده , , Wonuk and Kim، نويسنده , , Yongchan، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2013
Pages :
8
From page :
877
To page :
884
Abstract :
A hybrid ground-source heat pump (HGSHP) is proposed to overcome the decrease in the performance of a ground-source heat pump (GSHP) at the degraded ground thermal condition. In this study, a performance comparison between the GSHP and the HGSHP with parallel and serial configurations was conducted by varying the leaving fluid temperature (LFT) of the ground heat exchanger (GHEX), the fluid flow rate of the supplemental loop, the mean outdoor bin temperature, and the switching temperature of the hybrid operation. At the LFT of the GHEX of 40 °C, the coefficient of performances (COPs) for the HGSHP with the parallel and serial configurations were 18% and 6% higher than that of the GSHP, respectively. The cooling seasonal performance factors (CSPFs) of the HGSHPs with the parallel and the serial configurations were 6.5% and 2.0% higher, respectively, than that of the GSHP for Daegu city in South Korea.
Keywords :
configuration , COP , Heat rejection ratio , Hybrid ground-source heat pump , Cooling seasonal performance factor , Ground thermal degradation
Journal title :
Applied Energy
Serial Year :
2013
Journal title :
Applied Energy
Record number :
1605928