Title of article :
Heat transfer analysis of short helical borehole heat exchangers
Author/Authors :
Zarrella، نويسنده , , Angelo and De Carli، نويسنده , , Michele، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2013
Pages :
15
From page :
1477
To page :
1491
Abstract :
In this paper a numerical model to analyze the thermal behaviour of vertical ground heat exchangers with a helical shaped pipe is presented. This type of configuration can be a suitable alternative to conventional ground heat exchangers, especially when the heating and cooling loads of the building are very low. del describes the heat transfer problem by means of a network of interconnected thermal resistances and capacitances. Moreover, as the investigated ground heat exchanger is usually installed in shallow depth, the model takes into account the interaction between the ground and the ambient environment which affects the fluid heat carrier temperature into the heat exchanger and, as a consequence, the energy efficiency of the heat pump. a sensitivity analysis on the mesh parameters, the presented model is compared with experimental data and the simulation results show good agreement with the measurements. Finally, analyses to investigate the influence of the weather conditions, of the axial heat transfer and of the pitch between the turns of the helical pipe for two types of ground are carried out.
Keywords :
Numerical simulation , heat transfer , Ground source heat pump systems , ground heat exchanger , borehole , Helical pipe
Journal title :
Applied Energy
Serial Year :
2013
Journal title :
Applied Energy
Record number :
1605986
Link To Document :
بازگشت