Title of article
The selection of volume ratio of two-stage rotary compressor and its effects on air-to-water heat pump with flash tank cycle
Author/Authors
Ko، نويسنده , , Younghwan and Park، نويسنده , , Sangkyoung and Jin، نويسنده , , Simon and Kim، نويسنده , , Byungsoon and Jeong، نويسنده , , Ji Hwan، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2013
Pages
10
From page
187
To page
196
Abstract
A conventional heat pump exhibits performance degradation even though larger heating capacity is needed as the outdoor temperature declines. As a way to prevent the performance degradation, a heat pump with an inverter-driven two-stage rotary compressor and vapor injection (VI) cycle was investigated for an air-to-water heat pump (AWHP) system employing a flash tank. The volume ratio of two cylinder of a two-stage rotary compressor has significant effect on the performance of the AWHP so that it was experimentally investigated. Based on this result, a two-stage rotary compressor designed with an optimized volume ratio was manufactured and incorporated into the AWHP system. It was found that the VI AWHP system improved the heating capacity by 48% and the COP by 36% compared to those values for the conventional AWHP at water temperature of 60 °C and ambient temperature of −15 °C. This VI AWHP system can be used for cold climate applications.
Keywords
Two-stage rotary compressor , Volume ratio , Vapor injection , Air-to-water heat pump , Flash tank
Journal title
Applied Energy
Serial Year
2013
Journal title
Applied Energy
Record number
1606076
Link To Document