Title of article :
Performances of air source heat pump system for a kind of mal-defrost phenomenon appearing in moderate climate conditions
Author/Authors :
Wang، نويسنده , , W. and Feng، نويسنده , , Y.C. and Zhu، نويسنده , , J.H. and Li، نويسنده , , L.T. and Guo، نويسنده , , Q.C. and Lu، نويسنده , , W.P.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2013
Pages :
8
From page :
1138
To page :
1145
Abstract :
To quantify the performance drop of the air source heat pump (ASHP) system under a special kind of mal-defrost phenomenon appearing in moderate climate conditions, a field test was conducted for 8 days at the initial stage of a heating season in Beijing, China. The mal-defrost was found with the more than 60% frosted area of the outdoor heat exchanger after the system running 5 days. During this frosting period, the system COP was significantly degraded, only 2.3 under an environment temperature of 7.9 °C. Comparing the test data before and after frosting, it was found that the mal-defrost decreased the COP up to 40.4% and the heating capacity to 43.4%. Such low energy efficiency continued quite a long time until the defrost control was started up manually by the authors. After defrosting, the COP reclaimed to the normal level of 5.0. The origins of this special mal-defrost phenomenon were discussed. And some suggestions were proposed to modify the current defrosting control strategy, which were helpful to avoid the mal-defrost problem in the current ASHP system and therefore improve the system performances.
Keywords :
Heating capacity , Mal-defrost , Air source heat pump , COP
Journal title :
Applied Energy
Serial Year :
2013
Journal title :
Applied Energy
Record number :
1606660
Link To Document :
بازگشت