• Title of article

    A combined effect absorption chiller for enhanced performance of combined cooling heating and power systems

  • Author/Authors

    Jayasekara، نويسنده , , Saliya and Halgamuge، نويسنده , , Saman K.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2014
  • Pages
    10
  • From page
    239
  • To page
    248
  • Abstract
    Most industrial waste heat (e.g. waste heat from engines) is available as two or more heat sources or in a wider temperature range. Additionally, solar thermal energy has a higher harnessing efficiency at low temperatures while its work potential increases with temperature. However, well-established absorption cooling technologies, such as single and double effect absorption chillers, operate in relatively narrow firing temperature ranges. The use of the maximum temperature range of the sources or of multiple sources together increases the energy harnessing efficiency as well as the productivity of the absorption technology. aper introduces a combined effect absorption cycle that can utilize two energy sources at different temperature ranges or a single source at a wide temperature range. This new method reduces the capital investment and the operation costs of two conventional cycles that would otherwise have to be deployed in a series for an efficient energy conversion from heat to the cooling energy. The simulation results show that the proposed cycle improved the coefficient of performance (COP) of the system by 11% compared to the conventional separate production of the same capacity at the same temperature intervals.
  • Keywords
    Absorption cycle , CCHP , MODELING , LiBr–H2O , Combined effect , diffusion
  • Journal title
    Applied Energy
  • Serial Year
    2014
  • Journal title
    Applied Energy
  • Record number

    1608107