Title of article :
Maximum temperature to withstand water film for tempered glass exposed to fire
Author/Authors :
Shao، نويسنده , , Guangzheng and Wang، نويسنده , , Qingsong and Zhao، نويسنده , , Han and Wang، نويسنده , , Yu and Chen، نويسنده , , Haodong and Su، نويسنده , , Yanfei and Sun، نويسنده , , Jinhua and He، نويسنده , , Linghui، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2014
Pages :
9
From page :
15
To page :
23
Abstract :
Improper activation of the sprinkler or the cold water sprayed from the fire-fighting lance may accelerate the crack even fallout of the heated glass when encounter a fire. The objective of this work is to investigate the maximum temperature to withstand water film for tempered glass exposed to fire, and to find a way to keep the glass integration when the temperature exceeds the maximum endurance. Twenty-six tests were conducted in this study. The water film was not opened throughout in the control group. In other tests, the water film was opened when the maximum glass temperature reached different values. The only difference is the water film sprayed on the exposed glass surface in protection-cooling-type water film tests, but formed 20 mm apart from the hot surface in fire-separating-water-film tests. The results illustrate that the critical temperature, or a temperature scope, for 6 mm tempered glass to withstand water film is a value or range of value approaching 250 °C. It is also found that crazing of tempered glass generally occurs in the rapid cooling process, rather than the rapid heating process. The thermal shock caused by the sudden cooling can account for this phenomenon. The fire-separating-type water film was proved to be effective to protect glazing when its temperature outnumbered the critical value.
Keywords :
Tempered glass , fire , Water film , Thermal shock , critical temperature
Journal title :
Construction and Building Materials
Serial Year :
2014
Journal title :
Construction and Building Materials
Record number :
1636218
Link To Document :
بازگشت