Title of article :
The development of compressor-driven metal hydride heat pump (CDMHHP) system as an air conditioner
Author/Authors :
Park، نويسنده , , Jeong-Gun and Han، نويسنده , , Sang-Cheol and Jang، نويسنده , , Hwan-Yong and Lee، نويسنده , , Sangmin and Lee، نويسنده , , Paul S. and Lee، نويسنده , , Jai-Young، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2002
Pages :
4
From page :
941
To page :
944
Abstract :
The compressor-driven metal hydride heat pump (CDMHHP) using commercialized oil-type compressor is built to demonstrate the practical applicability of metal hydride air-conditioning system. Extensive research has been carried out on the design, construction and operating performance of the system. The experimental results indicate that the present CDMHHP can produce a maximum cooling power of 353 kcal/kg-alloy h and an energy efficiency (COP) of 1.8 with a half-cycle time of 3 min. The minimum cooling temperature is 6°C at 7 Nm3/min airflow rate.
Keywords :
metal hydride , CDMHHP system , Compressor , COP , Cooling power
Journal title :
International Journal of Hydrogen Energy
Serial Year :
2002
Journal title :
International Journal of Hydrogen Energy
Record number :
1649189
Link To Document :
بازگشت