Title of article
Natural and forced ventilation study in an enclosure hosting a fuel cell
Author/Authors
Cerchiara، نويسنده , , G.M. and Mattei، نويسنده , , N. and Schiavetti، نويسنده , , M. N. Carcassi، نويسنده , , M.N.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2011
Pages
11
From page
2478
To page
2488
Abstract
The purpose of the experimental work described in this paper is the determination of the ventilation requirements in enclosures containing fuel cells such that, in the case of a small non catastrophic release, the H2 concentration in air for zone 2 ATEX (2% v/v) is not exceeded. A full scale fuel cell was placed inside the experimental facility having 25 m3 volume. Three different leaks were investigated (40, 90 and 180 Nlt/min) and H2 concentrations were measured at five locations inside the facility. Several vent areas were examined for the cases of natural ventilation. When natural ventilation failed to ensure H2 concentrations less than 2% v/v in the facility, mechanical ventilation using two fans was investigated.
on the experimental set up, it was found that natural ventilation is sufficient when the air-flow calculated from ATEX guidelines is higher than 0.009 m3/s and the release flow rate corresponds to a non-catastrophic release, i.e. 40 Nlt/min. For higher release flow rates most of the ventilation configurations were not sufficient to maintain a H2 concentration less than 2% v/v.
rced ventilation configurations examined (together with the free ventilation areas used) were sufficient to maintain a H2 concentration below 2% v/v for 40 Nlt/min and 90 Nlt/min release flow rates. For the higher release flow rate of 180 Nlt/min, most of the forced ventilation configurations were insufficient.
Keywords
ventilation , Fuel cell , Hydrogen distribution , EXPERIMENTS
Journal title
International Journal of Hydrogen Energy
Serial Year
2011
Journal title
International Journal of Hydrogen Energy
Record number
1664596
Link To Document