Title of article :
Realistic minimum desorption temperatures and compressor sizing for activated carbon + HFC 134a adsorption coolers
Author/Authors :
Srinivasan، نويسنده , , Kandadai and Dutta، نويسنده , , Pradip K. Saha، نويسنده , , Bidyut Baran and Ng، نويسنده , , Kim Choon and Prasad، نويسنده , , Madhu، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2013
Abstract :
A low thermal diffusivity of adsorption beds induces a large thermal gradient across cylindrical adsorbers used in adsorption cooling cycles. This reduces the concentration difference across which a thermal compressor operates. Slow adsorption kinetics in conjunction with the void volume effect further diminishes throughputs from those adsorption thermal compressors. The problem can be partially alleviated by increasing the desorption temperatures. The theme of this paper is the determination the minimum desorption temperature required for a given set of evaporating/condensing temperatures for an activated carbon + HFC 134a adsorption cooler. The calculation scheme is validated from experimental data. Results from a parametric analysis covering a range of evaporating/condensing/desorption temperatures are presented. It is found that the overall uptake efficiency and Carnot COP characterize these bounds. A design methodology for adsorber sizing is evolved.
Keywords :
Activated carbon , Adsorption system , Compression , R134a , efficiency
Journal title :
Applied Thermal Engineering
Journal title :
Applied Thermal Engineering