Title of article
Drop-in energy performance evaluation of R1234yf and R1234ze(E) in a vapor compression system as R134a replacements
Author/Authors
Mota-Babiloni، نويسنده , , Adriلn and Navarro-Esbrي، نويسنده , , Joaquيn and Barragلn، نويسنده , , ءngel and Molés، نويسنده , , Francisco and Peris، نويسنده , , Bernardo، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2014
Pages
7
From page
259
To page
265
Abstract
This paper presents an energy performance evaluation of two low-GWP refrigerants, R1234yf and R1234ze(E), as drop-in replacements for R134a. Tests are carried out in a monitored vapor compression system combining different values of evaporation and condensation temperature, and without/with the adoption of an internal heat exchanger. The parameters analyzed are volumetric efficiency, cooling capacity and COP and they are presented taking R134a as baseline. Results show that without IHX the average volumetric efficiency for R1234yf and R1234ze is 4% and 5% lower compared with R134a. The cooling capacity obtained with R1234yf and R1234ze is reduced, with an average difference of 9% and 30% without IHX. Also, COP values are about 7% lower for R1234yf and 6% lower for R1234ze than those obtained using R134a. Finally, the use of an internal heat exchanger reduces the COP differences for both replacements.
Keywords
Drop-in , Energy performance , R1234yf , R1234ze(E) , R134a , Vapor compression system
Journal title
Applied Thermal Engineering
Serial Year
2014
Journal title
Applied Thermal Engineering
Record number
1907974
Link To Document