Title of article :
Experimental evaluation of a R134a/CO2 cascade refrigeration plant
Author/Authors :
Jorge and Sanz-Kock، نويسنده , , Carlos and Llopis، نويسنده , , Rodrigo and Sلnchez-Lajusticia، نويسنده , , Daniel and Cabello، نويسنده , , Ramَn and Torrella، نويسنده , , Enrique، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2014
Abstract :
We present the experimental evaluation of a R134a/CO2 cascade refrigeration plant designed for low evaporation temperature in commercial refrigeration applications. The test bench incorporates two single-stage vapour compression cycles driven by semi hermetic compressors coupled thermally through two brazed plate cascade heat exchangers working in parallel and controlled by electronic expansion valves. The experimental evaluation (45 steady-states) covers evaporating temperatures from −40 to −30 °C and condensing from 30 to 50 °C. In each steady-state, we conducted a sweep of the condensing temperature of the low temperature cycle with speed variation of the high temperature compressor. Here, the energy performance of the plant is analysed, focussing on the compressorsʹ performance, temperature difference in the cascade heat exchanger, cooling capacity, COP and compressors discharge temperatures.
Keywords :
Low GWP , Carbon dioxide , Energy efficiency , Cascade , two-stage , R134a
Journal title :
Applied Thermal Engineering
Journal title :
Applied Thermal Engineering