Title of article :
A novel low-temperature absorption–compression cascade refrigeration system
Author/Authors :
Xu، نويسنده , , Yingjie and Chen، نويسنده , , Fusheng and Wang، نويسنده , , Ya-qin and HAN، نويسنده , , Xiaohong and Li، نويسنده , , Dahong and Chen، نويسنده , , Guangming، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2015
Abstract :
This paper presents a novel absorption–compression cascade refrigeration system, which can reach an evaporating temperature of −170 °C. In the cascade system, the refrigerant of compression subsystem (CS) is subcooled by the refrigerant of low-grade heat driven absorption subsystem (AS) to reduce the electric power consumption. Theoretical and experimental investigations were carried out over the CS evaporating temperature ranging from −100 to −170 °C and operating parameters were given. At the CS evaporating temperature of −170 °C, when AS provided a low-grade cooling capacity of 164.8 W to CS, a decrease of 2.5 °C in CS evaporating temperature or an increase of 32.3 W in high-grade cooling capacity of CS were observed. Meanwhile, in CS, the discharge temperature and pressure decreased, while the suction pressure increased. These beneficial results not only verified the feasibility of the system, but also revealed the application potential of the system in the future.
Keywords :
Absorption–compression , Refrigeration , Cascade , Low-temperature , Mixed refrigerant
Journal title :
Applied Thermal Engineering
Journal title :
Applied Thermal Engineering