Title of article :
Cryogenic control system of the large COMPASS polarized target
Author/Authors :
Gautheron، نويسنده , , F. and Ball، نويسنده , , J. and Baum، نويسنده , , G. and Berglund، نويسنده , , P. and Doshita، نويسنده , , N. and Goertz، نويسنده , , St. and Gustafsson، نويسنده , , K. and Horikawa، نويسنده , , N. and Kisselev، نويسنده , , Y. and Koivuniemi، نويسنده , , Helen J. and Kondo، نويسنده , , K. and Meyer، نويسنده , , W. and Reicherz، نويسنده , , G.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Pages :
6
From page :
147
To page :
152
Abstract :
The dilution refrigerator used to cool the large COMPASS polarized target is monitored through a PC running LabVIEWTM 6.1 under Windows 2000TM. About 60 parameters of the target (temperatures, pressures, flow rates) are continuously plotted and checked. They are periodically recorded in an OracleTM database and in a data file. An alarm for every parameter can be individually activated and optionally connected to a GSM (Global System for Mobile Communication) delivery message system. A web server receives and publishes the online status of the target with online tables and graphics on a dedicated COMPASS polarized target information web site. A Siemens programmable logic controller (PLC) powered by an uninterruptable source keeps the cryogenic system safe and stable during the long beam periods by controlling valves and interlocks. This safety feature protects the dilution refrigerator against potential damages in case of power failure.
Keywords :
Slow control , Dilution refrigerator , COMPASS , Polarized target
Journal title :
Nuclear Instruments and Methods in Physics Research Section A
Serial Year :
2004
Journal title :
Nuclear Instruments and Methods in Physics Research Section A
Record number :
2202930
Link To Document :
بازگشت