Title of article
Photon-beam stabilization systems for the MX2 beamline at LNLS
Author/Authors
Sanfelici، نويسنده , , Lucas and de Mattos، نويسنده , , Fernando، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2011
Pages
4
From page
97
To page
100
Abstract
The MX2, a wiggler beamline dedicated to macromolecular crystallography, started routinely operating for users in 2007. Late in the commissioning phase, several experiments started to be conducted in order to characterize photon-beam stability. At that time, position movements of typically 150 μm per shift and severe energy drifts reaching 0.8 eV/h were observed at sample position, which would certainly spoil the MAD experiments. The severity of this scenario for a recently delivered beamline led us to install temperature sensors and inclinometers along the optical hutch, besides performing exhaustive tests to clarify the disturbance paths. To elucidate the main instability mechanisms, three control systems for beam stabilization were considered—position stabilization, ground motion canceling and, the most important of all, temperature control for the optical hutch. Results and perspectives are presented hereafter.
Keywords
LNLS , Protein Crystallography , control systems , Ground motion , Beam stability , Diagnostics , Beamline
Journal title
Nuclear Instruments and Methods in Physics Research Section A
Serial Year
2011
Journal title
Nuclear Instruments and Methods in Physics Research Section A
Record number
2208765
Link To Document