    Improved energy performance of air cooled centrifugal chillers with variable chilled water flow

  • Author/Authors

    Yu، نويسنده , , F.W. and Chan، نويسنده , , K.T.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2008
  • Pages
    17
  • From page
    1595
  • To page
    1611
  • Abstract
    This paper considers how to apply optimum condensing temperature control and variable chilled water flow to increase the coefficient of performance (COP) of air cooled centrifugal chillers. A thermodynamic model for the chillers was developed and validated using a wide range of operating data and specifications. The model considers real process phenomena, including capacity control by the inlet guide vanes of the compressor and an algorithm to determine the number and speed of condenser fans staged based on a set point of condensing temperature. Based on the validated model, it was found that optimizing the control of condensing temperature and varying the evaporator’s chilled water flow rate enable the COP to increase by 0.8–191.7%, depending on the load and ambient conditions. A cooling load profile of an office building in a subtropical climate was considered to assess the potential electricity savings resulting from the increased chiller COP and optimum staging of chillers and pumps. There is 16.3–21.0% reduction in the annual electricity consumption of the building’s chiller plant. The results of this paper provide useful information on how to implement a low energy chiller plant.
  • Keywords
    Centrifugal compressor , SIMULATION , Coefficient of Performance , Pumping system , Condensing temperature control
  • Journal title
    Energy Conversion and Management
  • Serial Year
    2008
  • Journal title
    Energy Conversion and Management
  • Record number

    2333888